UPS System, High
Frequency UPS 20K, 30K, 40kVA
Input: 380/400/415VAC
Output: 380/400/415VAC
1: High frequency UPS
2: GIBT, PWM technology
3: Bypass function
4: CE&ISO
Key
features
N+X parallel redundancy (compatible to battery share in the
parallel mode) The maximum of the inbuilt parallel mode is 8
UPS without any other external accessories, which helps the
customer to extend the system capacity with low cost.
N+X parallel redundancy (compatible to battery share in the
parallel mode) The maximum of the inbuilt parallel mode is 8
UPS without any other external accessories, which helps the
customer to extend the system capacity with low cost.
Intelligent management of battery charging and
discharging
Frontal-board operation and maintenance
Twin-channel line input. The UPS provides customer security
in power supply with intelligent choice between two-line
input or one-line input according to the actual
condition.
Remote monitoring. Communication interfaces like RS232/RS485,
Intelligent Slot are available for the realization of remote
management and monitoring. In addition, the optional AS400
card is suitable for the connection of stem point, which
enriches the customers choice out of the monitoring
demand
High-efficient DSP chip
Excellent performance in industrial environment protection.
Just with the standard product, IP21 protection level (
protecting the machine from the intrusion of solid material
with the diameter larger than 12mm or the water drops) is
achieved.
Application: Metro, Oil field, Army, Banks,
Telecommunication, Power
Plants and so on.
Photos:
Specification:
Online UPS Model
|
EX3320K
|
EX3330K
|
EX3340K
|
EX3360K
|
EX3380K
|
Rated Capacity
|
20KVA/16KW
|
30KVA/24KW
|
40KVA/32KW
|
60KVA/48KW
|
80KVA/64KW
|
Input
|
Voltage
|
210-475VAC
|
Frequency
|
40-70Hz
|
|
Phase Line
|
Three-phase 4 line + earth line
|
THDI
|
<3%
|
Input Power Factor
|
>0.99
|
Twin-channel Line Input
|
Yes
|
Battery
|
Type
|
Valve-regulated lead-acid storage battery
|
Standby Time
|
Depended by external battery bank
|
Output
|
Voltage
|
380VAC / 220 VAC
|
Frequency
|
50/60Hz
|
Phase line
|
Three-phase 4 line + earth line
|
Rated output power factor
|
0.8
|
Overload Capacity
|
125% maintain 10minutes
|
150% maintain 1minutes
|
Efficiency
|
Line Input Mode
|
93%
|
94%
|
BAT Mode
|
93%
|
94%
|
ECO Mode
|
98%
|
Intelligent Speed Control of Fan
|
yes
|
Display Device
|
LCD
|
I/O voltage, current, frequency, BAT voltage,
charging current value, discharging current value,
fault display, fault, warning
|
LED
|
The operation state of UPS
|
Warning Devices
|
Two ways of alerting: BUZZER sound, lamp signal,
|
Communication Interface
|
RS232, AS400, RS485, Service, EPO, BAT temperature
compensation, Intelligent Slot
|
Operation
|
Temperature
|
0-40centi-degree
|
Environment
|
Humidity
|
<95% (non condesing)
|
Weight
|
Net weight(include transformer)
|
82Kg/208Kg
|
110Kg/275Kg
|
114Kg/314Kg
|
282Kg
|
306Kg
|
Gross weight(include transformer)
|
122Kg/248Kg
|
160Kg/325Kg
|
164Kg/364Kg
|
356Kg
|
380Kg
|
Size L*W*H(mm)
|
643×420×925
|
710×470×1150
|
800×600×1850
|
Contact